Notifier Master Control Panel 5 zone c/w Battery SFP 5UD
Rp20.645.625
Store:
Semarang

Pilihan Kota Lain
Deskripsi
AC Power – TB1:
- SFP-5UD (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A. - Initiating Device Circuits – TB4 (and TB 6 on SFP-10UD
only): - Alarm Zones 1 – 5 on TB 4 (SFP-5UD and SFP-10UD).
- Alarm Zones 6 – 10 on TB6 (SFP-10UD only).
- Supervised and power-limited circuitry.
- Operation: All zones Style B (Class B).
- Normal Operating Voltage: Nominal 20 VDC.
- Alarm Current: 15 mA minimum.
- Short Circuit Current: 40 mA max.
- Maximum Loop Resistance: 100 ohms.
- End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 ULlisted).
- Standby Current: 2 mA.
- Refer to the Notifier Device Compatibility Document for listed
compatible devices
Informasi Tambahan
Berat | 10 kg |
---|
Hanya pelanggan yang sudah login dan telah membeli produk ini yang dapat memberikan ulasan.
Mungkin Kamu Suka
Notifier Master Control Panel 5 zone c/w Battery SFP 5UD
Rp20.645.625
Store:
Semarang

Pilihan Kota Lain
Deskripsi
AC Power – TB1:
- SFP-5UD (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A. - Initiating Device Circuits – TB4 (and TB 6 on SFP-10UD
only): - Alarm Zones 1 – 5 on TB 4 (SFP-5UD and SFP-10UD).
- Alarm Zones 6 – 10 on TB6 (SFP-10UD only).
- Supervised and power-limited circuitry.
- Operation: All zones Style B (Class B).
- Normal Operating Voltage: Nominal 20 VDC.
- Alarm Current: 15 mA minimum.
- Short Circuit Current: 40 mA max.
- Maximum Loop Resistance: 100 ohms.
- End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 ULlisted).
- Standby Current: 2 mA.
- Refer to the Notifier Device Compatibility Document for listed
compatible devices
Informasi Tambahan
Berat | 10 kg |
---|
Ulasan
Belum ada ulasan.